Analisa Unjuk Kerja Grid Tied Inverter Terhadap Pengaruh Radiasi Matahari dan Suhu PV pada PLTS On-Grid

Safri Nahela, Ivan Fauzi Faridyan, Noviadi Arief Rachman, Agus Risdiyanto, Bambang Susanto

Abstract


AbstractSolar radiation and temperature in photovoltaic (PV) can affect the output voltage and current of PV so that it also relates to the performance of the Grid Tied Inverter (GTI) on the on-grid PV system. This paper discusses the performance of the GTI based on output power on solar radiation and PV temperature. The method used in this testing was measuring simultaneously against the current and voltage parameters on PV, the current and voltage of the GTI, and the radiation and temperature of PV. Measurement with a data logger was also carried out on the above parameters in the morning and evening to find out at least the PV output voltage and current when the GTI starts or stops sending the power. The measurement results obtained that the GTI output power is affected by solar radiation and PV temperature. On the same radiation when the PV temperature gets higher, the PV voltage will drop, but the PV current and GTI current will increase. In addition, if with the same radiation and temperature but the AC source voltage was greater, the output power of GTI would also increase. The power produced by the GTI was lower than PV power due to GTI losses. The efficiency of the GTI decreases not only because of the increase in temperature above 35 oC but also due to the decreasing grid voltage. GTI starts sending power when the PV current was more than 2 A at 06.23 AM. GTI stops operating when the PV current was less than 1.74 A at 05.53 PM.


Keywords


Radiasi Matahari; Suhu PV; Tegangan PLN; Daya GTI.

Full Text:

PDF

References


Subandi and S. Hani, “Korelasi Suhu dan Intensitas Cahaya Teradap Daya pada Solar Cell,” Pros. Semin. Nas. Apl. Sains Teknol., pp. 31–40, 2014.

S. Nafis, M. Aman, and A. Hadiyono, “TENAGA SURYA PADA SISTEM KETENAGALISTRIKAN NIAS THE ECONOMIC ANALYSIS OF SOLAR SYSTEM POWER PLANT,” Ketenagalistrikan dan Energi Terbarukan, vol. 14, no. 2, pp. 83–94, 2015.

A. G. Wicaksena and B. Winardi, “Analisa Pengaruh Perubahan Temperatur dan Irradiasi pada Tegangan, Arus, dan Day keluaran PLTS,” TRANSIENT J. Ilm. Tek. Elektro UNDIP, vol. 6, no. 2, pp. 1–8, 2016.

R. Faulianur, I. D. Sara, and F. Arnia, “Simulasi Pelacakan Titik Daya Maksimum Modul Surya dengan Metode Grey Wolf Optimization,” J. Rekayasa Elektr., vol. 14, no. 36, 2018.

T. J. Mafu, “Modelling of Multi-State Panel Data : The Importance of the Model Assumptions by,” ELKHA, J. Tek. Elektro, vol. 5, no. December, pp. 23–26, 2014.

F. B. P, I. P. H, and R. F. I, “RANCANG BANGUN SISTEM PEMANTAU DAYA PADA MODUL SILIKON POLIKRISTAL DESIGN AND IMPLEMENTATION OF POWER MONITORING SYSTEM ON POLYCRYSTALLINE SILICON MODULE,” e-Proceeding Eng., vol. 4, no. 2, pp. 2114–2122, 2017.

M. Premkumar, K. Karthick, and R. Sowmya, “A Review on Solar PV Based Grid Connected Microinverter Control Schemes and Topologies,” Int. J. Renew. Energy Dev. 7, vol. 7, no. 2, pp. 171–182, 2018.

F. J. Gómez-gil, X. Wang, and A. Barnett, “Energy production of photovoltaic systems : Fixed , tracking , and concentrating,” Renew. Sustain. Energy Rev., vol. 16, no. 1, pp. 306–313, 2012.

T. Messo, T. Roinila, A. Aapro, and P. Rasilo, “Evaluation of Dead-Time Effect of Grid-Connected Inverters Using Broadband Methods,” IFAC-PapersOnLine, vol. 51, no. 15, pp. 449–454, 2018.

I. P. K. D. Putra, I. A. D. Giriantari, and I. W. A. Wijaya, “Perencanaan Sistem Jaringan Mikro ( Microgrid ) Dengan Supply Dari Pembangkit Listrik Tenaga Surya ( Plts ) Dan Generator Set Di Jurusan Teknik Elektro Universitas,” Teknol. Elektro, vol. 14, no. 2, 2015.

J. Eda, M. Mulyadi, B. Kartadinata, and H. Tanudjaja, “ANALISIS DAMPAK PEMASANGAN GRID TIE INVERTER INTERKONEKSI ANTARA JARINGAN PLN DAN SOLAR CELL T ERHADAP FAKTOR DAYA DAN HARMONISA SISTEM Program Studi Teknik Elektro – Fakultas Teknik Sistem demikian disebut sistem on grid . grid ini akan memiliki dampak k,” J. ELEKTRO, pp. 127–138.

E. M. Deschamps and R. Rüther, “Optimization of inverter loading ratio for grid connected photovoltaic systems,” Sol. Energy, vol. 179, no. December 2018, pp. 106–118, 2019.

I. W. G. A. Anggara, I. N. S. Kumara, and I. A. D. Giriantari, “Studi Terhadap Unjuk Kerja Pembangkit Listrik Tenaga Surya 1,9 Kw Di Universitas Udayana Bukit Jimbaran,” E-Journal SPEKTRUM, vol. 1, no. 1, pp. 118–122, 2014.




DOI: http://dx.doi.org/10.26418/elkha.v11i2.31452

Refbacks

  • There are currently no refbacks.


Copyright (c) 2019 Safri Nahela

 

Editorial Office/Publisher Address:
Editor Jurnal Elkha, Department of Electrical Engineering, Faculty of Engineering, Universitas Tanjungpura,
Jl. Prof. Dr. Hadari Nawawi, Pontianak 78124, Indonesia

website:http://jurnal.untan.ac.id/index.php/Elkha
email : jurnal.elkha@untan.ac.id

Assiciated with :

 

MoU FORTEI - ELKHA








                                            Flag Counter

 

                                                           

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.